Hitachi WJ200 Series Quick Reference Manual page 60

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Func.
Name
Code
B012
Level of electronic thermal
B212
Level of electronic thermal,
nd
2
motor
B013
Electronic thermal
characteristic
B213
Electronic thermal
characteristic, 2
b015
Free setting electronic thermal
~freq.1
b016
Free setting electronic thermal
~current1
b017
Free setting electronic thermal
~freq.2
b018
Free setting electronic thermal
~current2
b019
Free setting electronic thermal
~freq.3
b020
Free setting electronic thermal
~current3
B021
Overload restriction operation
mode
B221
Overload restriction operation
nd
mode, 2
motor
B022
Overload restriction level
B222
Overload restriction level,
nd
2
motor
B023
Deceleration rate at overload
restriction
B223
Deceleration rate at overload
nd
restriction, 2
motor
b024
Overload restriction operation
mode 2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
"b" Function
Set a level between 20% and 100%
for the rated inverter current.
Select from three curves, option
codes:
00...Reduced torque
nd
motor
01...Constant torque
02...Free setting
Range is 0 to 400Hz
Range is 0 to inverter rated current
Amps
Range is 0 to 400Hz
Range is 0 to inverter rated current
Amps
Range is 0 to 400Hz
Range is 0 to inverter rated current
Amps
Select the operation mode during
overload conditions, four options,
option codes:
00...Disabled
01...Enabled for acceleration and
constant speed
02...Enabled for constant speed
only
03...Enabled for acceleration and
constant speed, increase speed
at regen.
Sets the level of overload restriction,
between 20% and 200% of the rated
current of the inverter, setting
resolution is 1% of rated current
Sets the deceleration rate when
inverter detects overload, range is
0.1 to 3000.0, resolution 0.1
Select the operation mode during
overload conditions, four options,
option codes:
00...Disabled
01...Enabled for acceleration and
constant speed
02...Enabled for constant speed
only
03...Enabled for acceleration and
constant speed, increase speed
at regen.
Description
59
Run
Defaults
Mode
Lnitial data
Units
Edit
Rated
A
current for
A
each
inverter
model *1
01
01
0.0
Hz
0.00
Amps
0.0
Hz
0.00
Amps
0.0
Hz
0.00
Amps
01
01
Rated
Amps
current
x 1.5
Rated
Amps
current
x 1.5
1.0
sec.
1.0
sec.
01