Determining Wire and Fuse Sizes
The maximum motor currents in your application determines the recommended wore size.
The following table gives the wire size in AWG. The "Power Lines" column applies to the
inverter input power, output wires to the motor, the earth ground connection, and any other
components shown in the "Basic System Description" on page 2-7. The "Signal Lines"
column applies to any wire connecting to the two green connectors just inside the front
cover panel.
Motor Output
kW
HP
Inverter Model
VT CT VT CT
0.2 0.1
¼
1/8
WJ200-001SF
WJ200-002SF
0.4 0.2
½
¼
0.55 0.4
¾
½
WJ200-004SF
1.1 0.75 1.5
1
WJ200-007SF
WJ200-015SF
2.2 1.5
3
2
3.0 2.2
4
3
WJ200-022SF
WJ200-001LF
0.2 0.1
¼
1/8
0.4 0.2
½
¼
WJ200-002LF
WJ200-004LF
0.75 0.4
1
½
WJ200-007LF
1.1 0.75 1.5
1
WJ200-015LF
2.2 1.5
3
2
WJ200-022LF
3.0 2.2
4
3
WJ200-037LF
5.5 3.7
7.5
5
WJ200-055LF
7.5 5.5
10
7.5
11
7.5
15
10
WJ200-075LF
15
11
20
15
WJ200-110LF
WJ200-150LF
18.5 15
25
20
WJ200-004HF
0.75 0.4
1
½
1.5 0.75
2
1
WJ200-007HF
WJ200-015HF
2.2 1.5
3
2
3.0 2.2
4
3
WJ200-022HF
WJ200-030HF
4.0 3.0
5
4
5.5 4.0
7.5
5
WJ200-040HF
7.5 5.5
10
7.5
WJ200-055HF
WJ200-075HF
11
7.5
15
10
WJ200-110HF
15
11
20
15
WJ200-150HF
18.5 15
25
20
Note 1: Field wiring must be made by a UL-Listed and CSA-certified closed-loop terminal
connector sized for the wire gauge involved. Connector must be fixed by using
the crimping tool specified by the connector manufacturer.
Note 2: Be sure to consider the capacity of the circuit breaker to be used.
Note 3: Be sure to use a larger wire gauge if power line length exceeds 66ft. (20m).
Note 4: Use 18 AWG / 0.75mm
terminals).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Wiring
Power Lines
Signal Lines
2
AWG16 / 1.3mm
(75°C only)
2
AWG12 / 3.3mm
(75°C only)
2
AWG10 / 5.3mm
2
AWG16 / 1.3mm
2
AWG14 / 2.1mm
(75°C only)
2
AWG12 / 3.3mm
(75°C only)
2
AWG10 / 5.3mm
(75°C only)
AWG / 0.14
2
AWG6 / 13mm
to 0.75 mm
(75°C only)
shielded wire
2
AWG4 / 21mm
(see Note 4)
(75°C only)
2
AWG2 / 34mm
(75°C only)
2
AWG16 / 1.3mm
2
AWG14 / 2.1mm
2
AWG12 / 3.3mm
(75°C only)
2
AWG10/ 5.3mm
(75°C only)
2
AWG6 / 13mm
(75°C only)
2
AWG6 / 13mm
(75°C only)
2
wire for the alarm signal wire ([AL0], [AL1], [AL2]
10
Applicable
equipment
Fuse (UL-rated,
class J, 600V ,
Maximum
allowable current)
10A
20A
30A
10A
15A
20A
30A
18 to 28
2
60A
80A
80A
10A
15A
30A
50A
50A