Hitachi WJ200 Series Quick Reference Manual page 68

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Func.
Name
Code
C028
[AM] terminal selection
(Analog voltage output
0...10V)
C030
Digital current monitor
reference value
C031
Output [11] active state
C032
Output [12] active state
C036
Alarm relay active state
C038
Output mode of low current
detection
C039
Low current detection level
C040
Output mode of overload
warning
C041
Overload warning level
C241
Overload warning level, 2
motor
C042
Frequency arrival setting
for acceleration
C043
Frequency arrival setting
for deceleration
C044
PID deviation level
C045
Frequency arrival setting 2
for acceleration
C046
Frequency arrival setting 2
for deceleration
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
"C" Function
Description
11 programmable functions:
00...Output frequency
01...Output current
02...Output torque
04...Output voltage
05...Input power
06...Electronic thermal load ratio
07...LAD frequency
10...Heat sink temperature
11...Output torque (with code)
13...General output
16...Option
Current with digital current monitor
output at 1,440Hz
Range is 20%~200% of rated
current
Select logic conversion, two option
codes:
00...normally open [NO]
01...normally closed [NC]
Two option codes:
00...During acceleration,
deceleration and constant speed
01...During constant speed only
Set the level of low load detection,
range is 0.0 to 2.0*inverter rated
current
Two option codes:
00...During accel., decel. and
constant speed
01...During constant speed only
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
nd
Sets the overload warning signal
level between 0% and 200% (from
0 to two time the rated current of
the inverter)
Sets the frequency arrival setting
threshold for the output frequency
during acceleration,
range is 0.0 to 400.0 Hz
Sets the frequency arrival setting
threshold for the output frequency
during deceleration,
range is 0.0 to 400.0 Hz
Sets the allowable PID loop error
magnitude (absolute value),
SP-PV, range is 0.0 to 100%
Set range is 0.0 to 400.0 Hz
Set range is 0.0 to 400.0 Hz
67
Run
Defaults
Mode
Lnitial data
Units
Edit
07
[LAD]
Rated current
A
00
00
-
01
01
INV rated
A
current
01
Rated current
A
x 1.15
Rated current
A
x 1.15
0.0
Hz
0.0
Hz
3.0
%
0.00
Hz
0.00
Hz