Hitachi WJ200 Series Quick Reference Manual page 24

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

Sink/source logic of intelligent input terminals
Sink or source logic is switched by a short bar as below.
Sink logic
2
Wire size for control and relay terminals
Use wires within the specifications listed below. For safe wiring and reliability, it is
recommended to use ferrules, but if solid or stranded wire is used, stripping length should be
8mm.
Relay output terminal
Control logic
terminal
Relay terminal
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
1
L
PLC P24
Short bar
Solid
2
mm
(AWG)
0.2 to 1.5
(AWG 24 to 16)
0.2 to 1.5
(AWG 24 to 16)
23
Source logic
2
1
L
Short bar
Control logic terminal
Stranded
2
mm
(AWG)
0.2 to 1.0
(AWG 24 to 17)
0.2 to 1.0
(AWG 24 to 17)
PLC P24
8mm
Ferrule
2
mm
(AWG)
0.25 to 0.75
(AWG 24 to 18)
0.25 to 0.75
(AWG 24 to 18)

Hide quick links: