Func.
Name
Code
A092
Acceleration time (2)
A292
Acceleration time (2),
nd
2
motor
A093
Deceleration time (2)
A293
Deceleration time (2),
nd
2
motor
A094
Select method to switch to
Acc2/Dec2 profile
A294
Select method to switch to
Acc2/Dec2 profile, 2
A095
Acc1 to Acc2 frequency
transition point
A295
Acc1 to Acc2 frequency
transition point, 2
A096
Dec1 to Dec2 frequency
transition point
A296
Dec1 to Dec2 frequency
transition point, 2
A097
Acceleration curve selection
A098
Deceleration curve selection
A101
[OI] input active range start
frequency
A102
[OI] input active range end
frequency
A103
[OI] input active range start
current
A104
[OI] input active range end
current
A105
[OI] input start frequency
select
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
"A" Function
Duration of 2
acceleration, range is:
0.01 to 3600 sec.
Duration of 2
deceleration, range is:
0.01 to 3600 sec.
Three options for switching from
1st to 2nd accel/decel:
00
...2CH input from terminal
01
...Transition frequency
nd
motor
02
...Forward and reverse
Output frequency at which
Accel1 switches to Accel2, range
is 0.0 to 400.0 Hz
nd
motor
Output frequency at which
Decel1 switches to Decel2,
range is 0.0 to 400.0 Hz
nd
motor
Set the characteristic curve of
Acc1 and Acc2, five options:
00...linear
01...S-curve
02...U-curve
03...Inverse U-curve
04...EL S-curve
Set the characteristic curve of
Dec1 and Dec2, options are
same as above (a097)
The output frequency
corresponding to the analog
input range starting point,
range is 0.0 to 400.0 Hz
The output frequency
corresponding to the current
input range ending point,
range is 0.0 to 400.0 Hz
The starting point (offset) for the
current input range,
range is 0. to 100.%
The ending point (offset) for the
current input range,
range is 0. to 100.%
Two options; select codes:
00...Use offset (A101 value)
01...Use 0Hz
55
Run
Mode
Description
Edit
nd
segment of
nd
segment of
Defaults
Lnitial data
Units
10.00
sec
10.00
sec
10.00
sec
10.00
sec
00
00
0.0
Hz
0.0
Hz
0.0
Hz
0.0
Hz
00
00
0.00
Hz
0.0
Hz
20.
%
100.
%
00

Hide quick links: