3.3

Mounting the inverter

Please make sure the inverter is installed vertically, especially if it is installed outdoors.
>4"
(10 cm)
Figure 13: Inverter clearances
The National Electric Code may require significant larger working clearances (see NEC Section
110.26)
20
>20"
(50.8 cm)
>6"
(15.2 cm)
(15.2 cm)
Inverter should be mounted
>39"
at least 39" (100 cm) from
(100 cm)
the floor or ground surface.
Inverter should be at least
20" (50.8 cm) from any
ceiling surface
>6"
(15.2 cm)
(15.2 cm)