InfiniScale® IV 36-Port QSFP InfiniBand Switch User Manual
To extract a PSU:
1.
Remove the power cord from the power supply unit.
2.
Grasping the handle with your right hand, push the green latch release with your thumb while
pulling the handle outward. As the PSU unseats, the PSU status indicators will turn off.
3.
Remove the PSU.
To insert a PSU:
1.
Make sure the mating connector of the new unit is free of any dirt and/or obstacles.
2.
Insert the PSU by sliding it into the opening until a slight resistance is felt.
3.
Continue pressing the PSU until it seats completely. The latch will snap into place confirming
the proper installation.
4.
Insert the power cord into the supply connector.
Note: The green PSU indicator should light and the yellow indicator should remain off. If not, extract
the PSU and re-insert it again.

2.2.5 InfiniBand Cable Installation

All cables can be inserted or removed with the unit powered on. To insert a cable, press the connector into
the port receptacle until the connector is firmly seated. The GREEN LED indicator, below each QSFP port,
will light when the physical connection is established (that is, when the unit is powered on and a cable is
plugged into the port with the other end of the connector plugged into a functioning port). After plugging in
a cable, lock the connector using the latching mechanism particular to the cable vendor. When a logical con-
nection is made the yellow light will come on. When data is being transferred the yellow light will blink.
Cables in the bottom row should be inserted up side down in relation to the how the cables are inserted in
tehtop row.
Figure 10: Power Supply Unit Extraction
Mellanox Technologies
11
Rev 1.5