Ups Startup And Shutdown; Starting A Standalone Ups - Eaton BladeUPS User Manual

12 kva
Hide thumbs Also See for BladeUPS:
Table of Contents

Advertisement

OPERATION

UPS Startup and Shutdown

To start up or shut down a UPS, see:
S
S
S
S
S
S

Starting a Standalone UPS

To start a standalone UPS (see Figure 32 on page 49):
1.
NOTE The load connector breaker controls the load connector only, not the output power.
2.
3.
4.
5.
6.
7.
8.
78
EATON Powerware
Starting a Standalone UPS" on page 78
Starting a Parallel System" on page 80
Starting the UPS on Internal Bypass" on page 81
Standalone UPS Shutdown" on page 83
Individual Paralleled UPS Shutdown" on page 84
Parallel System Shutdown" on page 85
Verify that all UPS circuit breakers are in the OFF (O) position.
Verify that the UPS power cord is plugged in.
Switch on utility power where the UPS is connected.
Switch the UPS input circuit breaker to the ON (
Wait for the UPS front panel display to illuminate.
The
indicator flashes on the UPS.
Check the UPS front panel display for active alarms or notices
(other than Batteries Disconnected"). Resolve any active alarms
before continuing. See Troubleshooting" on page 119.
Switch the UPS battery circuit breaker to the ON (
If optional EBMs are installed, switch all EBM battery circuit
|
breakers to the ON (
) position.
®
BladeUPSt (12 kVA) User's Guide
|
) position.
S
164201649 Rev 3 www.powerware.com
|