Checking Pdu Indicators; Resetting The Pdu Network Connection - Dell Power Supply C8000 Owner's Manual

Table of Contents

Advertisement

Checking PDU Indicators

The PMC power/status and identification indicators lights to indicate an
error condition.
Power/status indicator blinks amber (about 1 Hz) to indicate an error
condition.
Identification indicator blinks blue (about 1 Hz).

Resetting the PDU Network Connection

By default, the PMC is configured to automatically obtain an IP address via
DHCP server.
1 Do three short presses of the reset button within 5 seconds to change the
DHCP IP address on the PMC over to a static IP address.
After the PMC resets, all network and configuration settings restore back
to their default values. The PMC is configured with the following default
network settings:
IP address: 192.168.0.120
Subnet mask: 255.255.255.0
Gateway: 192.168.0.1
The power/status indicator on the front of the PMC board displays the
following behaviors:
Blinking amber (500 ms off/5 s on) — Restarts the PMC firmware and
reset to factory default is completed.
Blinking amber (250 ms off/5 s on) — Restores the default network
settings to their default values.
2 Do three short presses of the reset button within 5 seconds again to switch
static IP back to reset to default (DHCP).
Updating Firmware Images and Monitoring the PDU Power Status