Air Inlet Temperature Threshold Settings
The table below lists the enclosure's air inlet temperature thresholds and the
different fan controller firmware actions for each threshold.
Table 5-6. Enclosure Air Inlet Temperature Threshold Settings
Enclosure
Threshold
Inlet
Setting
Condition
Normal
Upper
mode
non-recoverable
Upper critical
Upper
non-critical
Lower
non-critical
Lower critical
Lower
non-recoverable
Ambient
Threshold Level Action
Temp
43 °C
Extremely high Fan controller (FC)
°F)
(109.4
41 °C
High
°F)
(105.8
38 °C
Warning
°F)
(100.4
N/A
Warning
N/A
Low
5 °C
Extremely low Chassis status indicator
°F)
(41
firmware shuts down the
system.
NOTE:
The firmware reads
inlet temperature every 5 secs.
If the inlet temperature reaches
non-recoverable threshold, the
firmware will start to check the
power status for each sled and
initiate the sled for graceful
shutdown (pull-low 4 seconds).
Chassis status indicator
lights amber.
Temperature events are
recorded in the SEL.
Temperature events are
recorded in the SEL.
Chassis status indicator
lights amber.
lights amber.