6.3

Configuring the SMV 3000 with The SCT

Using the SCT for
SMV 3000
Configuration
ATTENTION
1/99
The SCT template files have tab cards that contain data fields for the SMV
parameters which you fill in. You start with the Device tab card to enter
the device tag name (Tag ID) and other general descriptions. Next, you
can select each tab card in order and configure each PV (PV1, secondary
variable if desired, PV2, PV3, and PV4).
SMV Process Variable
PV1 (Differential Pressure)
PV2 (Absolute Pressure or
Gauge Pressure) *
PV3 (Process Temperature)
PV4 (Flow)
* PV2 will be AP of GP depending on SMV model
Use the Flow Compensation Wizard to setup the SMV 3000 for flow
applications. The flow wizard guides you through the steps necessary to
complete your flow configuration. See Subsection 6.10 and Appendix C
for more information about the flow wizard.
In the subsections below information is given for filling in some of the
SCT tab card data fields. Supplementary background information and
reference data on SMV configuration that may be helpful is also
presented. Use the SCT on-line help and user manual for detailed "how to
configure" information.
If the transmitter detects an incomplete database upon power-up, it will
initialize the database parameters to default conditions. A setting or
selection with a superscript " d " in the following subsections identifies the
factory setting.
SMV 3000 Transmitter User's Manual
SCT Template Tab Card
DPConf
APConf or GPConf *
TempConf
FlowConf
49