Figure 28 Typical Pv1 Or Pv2 Range Calibration Hookup - Honeywell SMV 3000 User Manual

Smart multivariable transmitter
Hide thumbs Also See for SMV 3000:
Table of Contents

Advertisement

10.4
Calibrating PV1 and PV2 Range Values,
Procedure, continued
Figure 28
Typical PV1 or PV2 Range Calibration Hookup
SMV 3000
High
Pressure
Port
To High
To Low
Pressure
Pressure
Port
Port
* When using a pressure source
with an absolute readout device,
such as the ST 3000 transmitter
shown, you must calibrate the LRV
for the reference absolute pressure
(or ambient atmospheric pressure)
and the URV for the absolute
pressure span.
116
ME T ER
SI GNA L
L
Low
Pressure
Port
Dead Weight Tester
or
Precision Pressure Source
(For PV1 Calibration)
Vacuum/Gauge Source
or
Precision Pressure Source *
(For PV2 Calibration)
Absolute Pressure
Readout Device
(Smart Meter)
SMV 3000 Transmitter User's Manual
Continued
-
24Vdc
Power
250
Supply
+
+ Red
- Black
SCT
SFC
ST 3000 Model STA140
Absolute Pressure Transmitter
with Smart Meter
250
-
24Vdc
Power
Supply
+
Continued on next page