4.5
Wiring SMV 3000 Transmitter,
Lightning protection
Figure 17
1/99
When your transmitter is equipped with optional lightning protection, you
must connect a wire from the transmitter to ground as shown in Figure 17
to make the protection effective. We recommend that you use a size 8
AWG (American Wire Gauge) or KCM (Kilo Circular Mils) bare or
Green covered wire.
Note that protection for temperature sensor leads is not provided by the
optional lightning protection.
Ground Connection for Lightning Protection
Connect to
Earth Ground
SMV 3000 Transmitter User's Manual
Continued
Electronics
Housing
35