6.8
TempConf Configuration - PV3,
PV3 (Temperature)
Range Values
(LRV and URV)
Background
Figure 22
1/99
The Lower Range Value and the Upper Range Value fields for PV3 are
found on the TempConf tab card.
Set the LRV and URV (which are desired zero and span points for your
measurement range) for the process temperature input PV3 by typing in
the desired values on the TempConf tab card.
LRV = Type in the desired value (default = 0.0)
URV = Type in the desired value (default = URL)
You can set the LRV and URV for PV3 by either typing in the desired
values on the SCT TempConf tab card or applying the corresponding LRV
and URV input signals directly to the transmitter. The LRV and URV set
the desired zero and span points for your measurement range as shown the
example in Figure 22.
Typical Range Setting Values for PV3
Typical RTD Range Configuration
LRL
LRV
-328
-100
Range Limits
Measurement
Range
-328 to 842 o F
-100 to 600 o F
NOTE:
LRL and URL values are set automatically when you select the sensor type in
the Sensor Type field.
SMV 3000 Transmitter User's Manual
Continued
SPAN
URV
257
600
Lower Range
Upper Range
Value
Value
-100 o F
600 o F
Continued on next page
URL
842 o F
Span
700 o F