Buderus Logamax plus GB142-24 Servicing Instructions page 42

Condensing gas boiler
Hide thumbs Also See for Logamax plus GB142-24:
Table of Contents

Advertisement

7
Diagnosis
Hot water but no central heating continued -2
page 41
20
Check that the DHW circulation pump is
running, as described for the primary
circulation pump.
Is the
DHW circulation pump running?
Check that during heating mode there is a
120V AC voltage on the DHW circulation
pump.
Is there a
voltage?
Check the connection board to make sure that
there is 120V AC on both contacts L and N
of connection PS (green) during heating
mode.
Is
there a voltage?
Check the cable loom of
the device.
Is the cable loom
okay?
Replace the connection board.
Is the DHW circulation
pump running?
44
page 83
42
Logamax plus GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications!
Yes
No
Yes
No
Yes
No
No
Yes
Yes
No
48
page 43
49
page 43
Replace the supply cord of
the tank-filling pump.
Replace the
cable loom.
8
page 31