Boiler capacity
Type of gas supply
Natural gas H
24 kW
LPG P
Natural gas H
30 kW
LPG P
Natural gas H
45 kW
LPG P
Natural gas H
60 kW
LPG P
table 5
Gas orifice diameter
Type of gas
Factory setting of gas burner fitting
supply
H
Natural gas
Delivered factory-set to Wobbe index
14.1 kWh/m
14.7 psi (=1,013 mbar)), suitable for
Wobbe index range 11.3 – 15.2 kWh/m
Information on gas type instruction plate:
Set to gas category: G 20 – 2E.
Previous indications: set to Wobbe index
15.0 kWh/m
(=1,013 mbar)), suitable for
Wobbe index range 12.0 – 15.7 kWh/m
P
LPG
Suitable for propane after conversion (also see
the chapter "Conversion to another type of gas
supply").
Information on gas type instruction plate:
Set to gas category: G 31 – 3P.
Table 6
Factory setting of gas burner fitting
The diameter of the gas orifice islocated on the gas orifice.
The article number of the Venturi is located on both clamps of
the Venturi (see fig. 111, pos. 1 and 2).
Logamax plus GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications!
Venturi article
number
423.072A
423.072A
423.072A
423.072A
423.170A
423.170A
423.173A
423.173A
3
(based on 59 °F (=15°C),
3
3
(based on 32 °F (=0°C), 14.7 psi
3
Gas orifice diameter Altitude 0 - 10,200 ft
No CO
correction
2
[inch]
0.175
0.132
0.175
0.132
0.213
0.163
0.295
0.213
.
.
fig. 111 Venturi article number
Altitude 4,001 - 10,200 ft
with CO
2
[mm]
[inch]
4.45
0.179
3.35
0.134
4.45
0.177
3.35
0.134
5.40
0.219
4.15
0.163
7.50
0.301
5.40
0.215
2
Appendix
9
correction
[mm]
4.55
3.40
4.50
3.40
5.55
4.15
7.65
5.45
1