7215 0300 - 02/2008 US/CA (en) For the user User’s Instructions Condensing gas boiler GB142-24/30/45/60 This manual must be retained for future use. Please read thoroughly before operating...
Page 2
The operating manual is part of the documentation that is delivered to the installation's operator. Go through the information in this manual with the owner/ operator and make sure that he or she is familiar with all the necessary operating instructions. http://www.buderus.net...
Starting up the boiler ....15 Shutting down the boiler ....18 http://www.buderus.net...
Page 4
About these instructions These user's Instructions contain important information for the safe and proper operation of GB142-24/30/45/60 condensing gas boilers. If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Indicates presence of hazards that will or outdoor reset control AM10 (scope of delivery), can cause minor personal injury or property a room controller RC35 (optional) or an On/Off damage. thermostat (accessory). CAUTION: Risk of electric shock. Indicates presence of hazards due to electric shock. http://www.buderus.net...
– Have a trained service provider check, clean but not related to personal injury or property and service the heating system once a year. damage. Buderus recommends a contract for annual service and maintenance. Safety instructions – The condensate collection and disposal system must be periodically cleaned by a trained Make sure to observe these safety instructions.
Page 7
– Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the boiler. http://www.buderus.net...
3: LED "DHW status" pos. 6: LED "Burner status" pos. 10: "Chimney sweep" button pos. 4: Display pos. 7: LED "Burner Operation" pos. 11: "Reset" button 1) ECO mode means that the temperature inside the hot water tank is 140 °F. http://www.buderus.net...
(see chapter 3 "Starting up and shutting down the boiler", page 15). Make yourself familiar with the location of the emergency shutoff switch and the boiler loop circuit breaker. http://www.buderus.net...
Table 1 Settings of "DHW temperature" knob This function has been optimized for boilers with combined DHW heating (combi-units). The LED under the rotary knob lights up if the DHW temperature is below the target value (heat request for DHW). http://www.buderus.net...
Table 3 Settings of "space heating water temperature" rotary knob The LED under the rotary knob lights up when the heating system is switched on and heat is requested. In summer mode the heating system is switched off (LED off). http://www.buderus.net...
The water in the boiler has reached the required temperature or there is no heat request. Table 4 LED indication Other functions and economic heating The functions described above are basic functions, carried out directly on the boiler using the Logamatic BC10 basic controller. http://www.buderus.net...
Starting up and shutting down the boiler Starting up and shutting down the boiler Starting up the boiler Turn the "space heating water temperature" and "DHW temperature" rotary knobs to "Aut" (automatic mode). The control unit will now take control. http://www.buderus.net...
Page 16
Open the boiler manifold shut-off valves (fig. 3, pos. 2). Fig. 3 Opening the gas shut-off valve and the boiler manifold shut-off valves pos. 1: gas shut-off valve pos. 2: boiler manifold shut-off valves http://www.buderus.net...
Page 17
(On). The basic controller checks the current system status and the burner becomes operational as soon as there is a heat request. This procedure takes approx. 30 seconds. Adjust the settings on the control unit (see the Operating Instructions for the control unit). http://www.buderus.net...
– Drain the heating system water from the lowest point of the heating system using the boiler drain. The vent screw at the highest point of the heating system must then be open. http://www.buderus.net...
Displaying operating messages In normal operating mode the display will show the current heater water temperature. You can display other information using the "Service" button. Push the "Service" button a number of times to switch between the various status displays. http://www.buderus.net...
Page 20
Standard display for this operating condition. This display appears after 5 minutes if no button is pushed. Other values may be displayed depending on the operating condition. You can return to the starting point by repea- tedly pushing the "Service" button. http://www.buderus.net...
Page 21
The gas valve is open Initializing, Pre Purge Flow temperature higher than set Table 5 Messages in normal operation mode Push the "Service" button to display this operation message. Is shown automatically, i. e. without you pushing a button. http://www.buderus.net...
Page 22
Alternating display codes indicates the current water pressure in psi. Contact the installer. Table 5 Messages in normal operation mode Push the "Service" button to display this operation message. Is shown automatically, i. e. without you pushing a button. http://www.buderus.net...
If the fault cannot be reset: Write down the error message and contact your heating equipment servicing company. Make sure that the heating system is not damaged by frost (see the safety instructions in chapter “Shutting down the boiler” on page 18). http://www.buderus.net...