8.1.2
External connection board fuse
Switch off the power supply of the heating system on the circuit
breaker.
Set the main switch on the BC10 to "0" (Off).
Remove the casing.
Remove the cover from the connection box (fig. 6).
Dismantle the fuse holder (fig. 7, pos. 10).
Remove the fuse from the fuse holder.
Check the circuit continuity through the fuse using the volt-ohm-
multimeter. If broken, replace it with a (new) ceramic fuse
5 amps, 250V fast blow (F5AH, 250V).
Re-install the cover on the connection box.
Fit the casing.
Switch on the power supply of the heating system on the circuit
breaker.
Set the main switch on the BC10 to "1" (On).
Logamax plus GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications!
fig. 6
Removing the cover from the connection box
RC FA WA FW EV
1
2
3
4
5
6
fig. 7
External connection board
pos. 1: RC Room thermostat (connection color orange)
pos. 2: Outdoor-temperature sensor (connection color
blue)
pos. 3: Potential-free On/Off thermostat (connection color
green)
pos. 4: DHW temperature sensor (connection color grey)
pos. 5: External switching contact, potential-free for floor
heating safety etc. (connection color red)
pos. 6: DO NOT USE
pos. 7: Primary loop pump 120V 60Hz (connection color
green)
pos. 8: DHW tank pump 120V 60Hz (connection color grey)
pos. 9: DHW recirculating pump 120V 60Hz (connection
color lilac)
pos. 10: main connection 120V 60Hz (connection color
white)
pos. 11: Fuse holder
Actions
8
11
PK
PS
PZ
Grid
7
8
9
10
85