Gas valve replacement Condensing gas boiler Instructions Required Input Rates Logamax plus GB162-80 kW Logamax plus GB162-100 kW 290,000 btu/hr 333,000 btu/hr This instruction is for replacing the gas valve for the GB162 model boilers with Natural Gas. WARNING! Replacement of a gas valve must be done by a qualified service...
Checking and adjusting the gas/air ratio Carrying out a tightness test in operating conditions Measuring the carbon monoxide content (CO) Lighting Instructions Operating Instructions Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
NOTICE: Indicates special instructions on installa- tion, operation or maintenance that are important but not related to personal injury or property damage. Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
– o-ring (fan-venturi) Table 1 Gas orifice diameter – sealing (gas pipe) – Torx keys Tx25 and Tx30 – Torx screws (flange). Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
Mains switch Open the boiler door by turning the vent key through ¼ rotation (fig. 2). fig. 2 Opening the boiler door Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
Page 6
Removing the connectors from the fan Pull the air suction tube from the fan (fig. 5). fig. 5 Pulling the air suction tube from the fan Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
Page 7
O-ring (fig. 9) and follow the instructions above in reverse order. fig. 9 Placing a new O-ring on the fan unit Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
Page 8
Close the boiler door and lock the fastener by turn- ing the vent key through ¼ rotation in a clockwise direction. fig. 12 Re-installing the burner plate Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
60 inch W.C. (150 mbar). fig. 13 Measuring the gas supply pressure Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
Page 10
– Install a gas pressure regulator before the gas burner fitting if the supply pres- sure is too high. Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
16 Setting the gas/air ratio Repeatedly press the "Service" button until the temperature indication is displayed. Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
You must establish and resolve the cause. The boiler must be operational when you do this. fig. 17 Measuring the carbon monoxide content Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
Connect the heating system to the power supply. Switch on the heating system using the main switch (fig. 18). fig. 18 Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
Page 15
Notes Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
Page 16
Bosch Thermotechnology Corporation 50 Wentworth Avenue Londonderry, NH 03053 Tel.: 603-552-1100 Fax: 603-584-1681 www.buderus.net Products manufactured by: Bosch Thermotechnik GmbH Sophienstrasse 30-32 D-35576 Wetzlar www.buderus.de Bosch Thermotechnology Corporation reserves the right to make changes without notice due to continuing engineering...