Buderus Logamax plus GB142-24 Servicing Instructions page 26

Condensing gas boiler
Hide thumbs Also See for Logamax plus GB142-24:
Table of Contents

Advertisement

6
Symptoms
Display code
z
z
Main
Sub-
display
display
code
code
e
e
[a/0/1|
[8/1/6|
e
e
[a/0/1|
[8/2/8|
e
e
[a/0/2|
[8/1/6|
e
e
[c/0/\|
[2/8/8|
e
e
[c/0/\|
[2/8/9|
e
e
[c/a/\|
[2/8/6|
e
e
[c/u/\|
[2/4/0|
e
e
[c/y/\|
[2/4/1|
e
e
[e/\/\|
[2/9/0|
+ any digit
or letter
e
e
[e/\/\|
[2/4/2|
to
+ any digit
or letter
[2/8/7|
[h/\/7|
e
e
[h/\/7|
[r/e/\|
table 2
Display indications on the BC10 basic controller
1)
only visible using the service tool
2)
is being carried out
6.2
LED on the UBA 3
In addition to the display indication on the BC10 basic controller, there is a red LED on the UBA 3.
The meaning of this LED is explained in see table 3.
LED
Off
Flashing slowly (1 Hz)
Flashing fast (10 seconds)
On
table 3
LED on the UBA 3
26
Logamax plus GB142-24/30/45/60 - We reserve the right to make any changes due to technical modifications!
Symptoms
z
Key to display code
e
No communication with EMS.
e
Water pressure sensor.
e
No communication with BC10.
e
The UBA 3 has no connection to the
pressure sensor or there is a short circuit.
e
Short circuit in connection to pressure
sensor.
e
The return sensor has measured a
temperature higher than 221 °F (105 °C).
e
The return sensor is shorted.
e
The return sensor contact is interrupted.
e
The UBA 3 is defective.
e
KIM or UBA 3 is defective.
The heating system pressure is too low.
The heating system pressure is too low.
Reset is carried out. After pressing the
"Reset" button this code is displayed for
5 seconds.
Meaning
Normal operation
There is a boiler fault (locking fault).
During startup after replacing the KIM or the UBA 3.
During a fault in the UBA 3 or if the KIM is not recognized.
Type of
Reset
Other
display
required
symptoms
code
?
AS
The boiler no
longer gets heat
requests; the
heating system no
longer heats.
AS
AS
BC10 settings are
no longer taken
over by RCxx
devices.
VKS
yes
No heating
operation and no
hot water.
VKS
yes
VKS
yes
VKS
yes
BKS
no
No heating
operation and
no hot water.
VKS
yes
No heating
operation and
no hot water.
SC
SC
2)
ÜC
Diagnosis
Remedy
EMS bus system
Reset by switching
is overloaded.
the heating system
on and off.
UBA 3/MC10 is
Inform the
defective.
BUDERUS
customer service
department if
necessary.
The digital water
Replace the digital
pressure sensor
water pressure
is defective.
sensor.
Contact problem
Check the BC10
at BC10 or BC10
connection.
is defective.
Replace the BC10
if necessary.
page 82
page 82
page 80
page 80
page 80
page 80
page 78
page 80
page 78
page 80