4.5 Basic Setting Commands
Dot model
UA p1,p2<terminator>
Syntax
p1 Record position selection
ZERO 0% position
FULL 100% position
Hysteresis
The difference in the record position
according to the operating direction of
the printer carriage
p2 Record position adjustment value
When p1 = Hysteresis
An integer between –7 to 7
When p1 = ZERO
RD100B: An integer between 0 and 15
RD1800B: An integer between 0 and 50
When p1 = FULL
RD100B: An integer between –30 to 30
RD1800B: An integer between –50 to 50
Example
Adjust the 100% position. Set the record
position adjustment value to 25.
UA FULL,25
Description • Carry out the adjustment in the following
order: P1 = Hysteresis, ZERO, and then
FULL.
• Check the recorded result and correct the
record position adjustment value.
• To end the adjustment, execute the UY0
command. If you do not end the adjustment,
you cannot change the execution mode.
• The unit for p2 is dot (0.1 mm).
YE
Exits from Basic Setting mode.
When the YE command is executed, communication is
dropped.
YE p1<terminator>
Syntax
p1 Apply/Discard the settings
STORE
ABORT
Example
Apply the basic settings.
YE STORE
Description Applies the settings changed with the basic
setting commands.
XE
Exits from Basic Setting mode.
Communication is not dropped when the XE command is
executed.
Syntax
XE p1<terminator>
p1 Apply/Discard the settings
STORE
ABORT
Example
Apply the basic settings.
XE STORE
4-24
(reference value: 1000)
(reference value: 1800)
Apply the settings
Discard the settings
Apply the settings
Discard the settings
Description The settings specified by the following
commands and saved using the XE command
take effect after the recorder is power cycled.
YS, YB, YA, YN, YD, YQ, and YK