Omega RD100B User Manual page 58

Programmable recorder communication interface
Hide thumbs Also See for RD100B:
Table of Contents

Advertisement

Description Use the format below to specify the display ON/
OFF state of each channel.
• List the values one after another for all
channels and separate the measurement
channels and computation channels with a
hyphen.
• Channels cannot be omitted.
• The characters after the hyphen are valid only
on models with the computation function (/M1
option).
For multiple display (display in which different
screens can be assigned to the top and bottom
sections
VD
Syntax
p1,p2,p3,p4,p5,p6,p7,p8,p9,p10,p11,p12<terminator>
p1 Screen number (01 to 15)
p2 Display type
Multiple display
Display in which different screens can
be assigned to the top and bottom
sections
p3 Top section display type
1CH digital
1-channel digital display
2CH digital
2-channel digital display
3CH digital
3-channel digital display (RD1800B)
TIME
Date/Time (RD100B)
Chart speed
Chart speed (RD100B)
TIME/Chart speed
Date/Time/Chart speed (RD1800B)
Channel alarm status
Channel alarm status display
STATUS
Status display
Light out
Screen OFF
Tag_1CH digital
1-channel digital display (tag)
Note
Parameters that become invalid due to p3, p4, p8, or p9
setting are skipped, and the next parameter is brought
forward.
p4 Displayed channel switching interval
Condition: Set this parameter when p3 is
1CH digital or 2CH digital.
MANUAL
Fixed display channels, data
update rate (pen model): 2 s,
data update rate (dot model):
scan interval
AUTO1S
Switch the displayed
channels and data every 1
second.
AUTO2S
Switch the displayed
channels and data every 2
seconds.
AUTO3S
Switch the displayed
channels and data every 3
seconds.
AUTO4S
Switch the displayed
channels and data every 4
seconds.
AUTO5S
Switch the displayed
channels and data every 5
seconds.
p5 Channel number
Condition: This parameter can be specified
when p3 is 1CH digital, 2CH digital,
or Tag_1CH digital and p4 is MANUAL.
p6 2nd channel number
Condition: This parameter is specified when
p3 is 2CH digital and p4 is MANUAL.
p7 3rd channel number
Condition: This parameter is specified when
p3 is 3CH digital and p4 is MANUAL.
p8 Bottom section display type
Same as p3
p9 Displayed channel switching interval
Same as p4
p10 Channel number
Same as p5
p11 2nd channel number
Same as p6
p12 3rd channel number
Same as p7
Query
VD[ p1]?
Example
Assign the display in which different screens can
be assigned to the top and bottom sections to
screen 09. Set the top section to status display
and the bottom section to 1-channel digital
display. Switch the displayed channel every 3
seconds (parameters p5 to p7, p10, and p12
explained above are omitted).
VD 09,Multiple display,STATUS,1CH
digital,AUTO3S
4.4 Setting Commands