Omega RD100B User Manual page 60

Programmable recorder communication interface
Hide thumbs Also See for RD100B:
Table of Contents

Advertisement

XB
Sets the burnout detection.
Syntax
XB p1,p2<terminator>
p1 Channel number
p2 The procedure taken when a sensor
burnout is detected
OFF Disable the burnout detection.
UP
Set the recording off the scale to the
right when a burnout is detected.
DOWN Set the recording off the scale to the
left when a burnout is detected.
XB[ p1]?
Query
Example
Set the recording off the scale to the right when a
sensor burnout is detected on channel 01.
XB 01,UP
XJ
Sets the RJC.
When using the internal compensation circuit
XJ p1,p2<terminator>
Syntax
p1 Channel number
p2 Reference junction compensation selection
(INTERNAL)
Query
XJ[ p1]?
Example
Use the internal compensation circuit on channel
01.
XJ 01,INTERNAL
When using an external RJC
Syntax
XJ p1,p2,p3<terminator>
p1 Channel number
p2 Reference junction compensation selection
(EXTERNAL)
p3 Compensation voltage (–20000 to 20000)
[µV]
Query
XJ[ p1]?
Example
Set the reference junction compensation of
channel 02 to external and set the compensation
voltage to 0 µV.
XJ 02,EXTERNAL,0
Description The unit of p3 is µV (microvolts).
UC
Changes the dot color (dot model).
UC p1,p2<terminator>
Syntax
p1 Channel number
p2 Dot color
PURPLE
RED
GREEN
BLUE
BROWN
BLACK
Query
UC[ p1]?
Example
Set the dot color of channel 06 to purple.
UC 06,PURPLE
Description On models with the computation function (/M1
option), the dot color of computation channels
can be changed.
4.5 Basic Setting Commands
UO
Sets the pen offset
compensation (pen model).
UO p1<terminator>
Syntax
p1 Pen offset compensation ON/OFF (ON, OFF)
Query
UO?
Example
Use the pen offset compensation.
UO ON
UP
Sets the items to be printed.
Pen model
Syntax
UP p1,p2,p3,p4,p5,p6<terminator>
p1 Channel number/tag selection
CHANNEL
Print the channel number
TAG
p2 Alarm printout
ON1 Print at alarm occurrence and release
ON2 Print at alarm occurrence
OFF Do not print
p3 Record start time printout ON/OFF (ON, OFF)
p4 New chart speed printout ON/OFF (ON, OFF)
p5 Scale printout ON/OFF (ON, OFF)
p6 Recording color printout ON/OFF (ON, OFF)
UP?
Query
Example
Print tags. Print all items.
UP TAG,ON1,ON,ON,ON,ON
Dot model
Syntax
UP p1,p2,p3,p4,p5,p6<terminator>
p1 Channel number/tag selection
CHANNEL
Print the channel number
TAG
p2 Channel number printout ON/OFF (ON,
OFF) by the trend recording
p3 Alarm printout
ON1 Print at alarm occurrence and release
ON2 Print at alarm occurrence
OFF Do not print
p4 Record start time printout ON/OFF (ON, OFF)
p5 New chart speed printout ON/OFF (ON, OFF)
p6 Scale printout ON/OFF (ON, OFF)
UP?
Query
Example
Print the channel numbers. Print all items.
UP CHANNEL,ON,ON1,ON,ON,ON
UR
Sets the periodic printout interval.
Syntax
UR p1,p2,p3,p4<terminator>
p1 Print interval mode
Auto
Automatically set the interval
according to the chart speed
Manual
Specify the interval
p2 Reference time (00 to 23 [hour])
p3 Interval (10min, 12min, 15min, 20min,
30min, 1h, 2h, 3h, 4h, 6h, 8h, 12h, 24h)
(when p1 is Manual)
4
Print the tag
Print the tag
4-19