Omega RD100B User Manual page 64

Programmable recorder communication interface
Hide thumbs Also See for RD100B:
Table of Contents

Advertisement

Example
Set the IP address to 192.168.111.24, the subnet
mask to 255.255.255.0, and the default gateway
to 0.0.0.0.
YA 192.168.111.24,255.255.255.0,
0.0.0.0
Description The settings specified by this command and
saved using the XE command take effect after
the recorder is power cycled.
YN
Sets the DNS (/C7 option).
When not using the DNS
YN p1<terminator>
Syntax
p1 Use/Not use the DNS (OFF)
YN?
Query
Example
Do not use the DNS.
YN OFF
When using the DNS
Syntax
YN p1,p2,p3,p4,p5<terminator>
p1 Use/Not use the DNS (ON)
p2 Address of the primary DNS server
(0.0.0.0 to 255.255.255.255)
p3 Address of the secondary DNS server
(0.0.0.0 to 255.255.255.255)
p4 Domain suffix 1 (up to 64 characters)
p5 Domain suffix 2 (up to 64 characters)
Query
YN?
Example
Use the DNS server at 192.168.0.1.
YN ON,192.168.0.1
Description The settings specified by this command and
saved using the XE command take effect after
the recorder is power cycled.
YD
Sets whether to use the login
function via communication
(/C7 option).
Syntax
YD p1<terminator>
p1 Use/Not use the login function via
communication (USE, NOT)
Query
YD?
Example
Use the login function via communication.
YD USE
Description The settings specified by this command and
saved using the XE command take effect after
the recorder is power cycled.
YQ
Sets the communication timeout
(/C7 option).
When not using the timeout
YQ p1<terminator>
Syntax
p1 Enable/Disable communication timeout (OFF)
Query
YQ?
Example
Disable timeout.
YQ OFF
When using the timeout
YQ p1,p2<terminator>
Syntax
4.5 Basic Setting Commands
p1 Enable/Disable communication timeout (ON)
p2 Timeout time (1 to 120) [minutes]
Query
YQ?
Example
Enable communication timeout and set the
timeout period to 3 min.
YQ ON,3
Description The settings specified by this command and
saved using the XE command take effect after
the recorder is power cycled.
YK
Sets keepalive (/C7 option).
YK p1<terminator>
Syntax
p1 Enable/Disable keepalive (ON, OFF)
YK?
Query
Example
Disable keepalive.
YK OFF
Description The settings specified by this command and
saved using the XE command take effect after
the recorder is power cycled.
UA
Sets the record position.
Pen model
UA p1,p2,p3<terminator>
Syntax
p1 Record position selection
ZERO
0% position
FULL
100% position
p2 Pen number (1 to 4)
p3 Record position adjustment value
When p1 = ZERO
When p1 = FULL
Example
Adjust the 0% position of pen 1. Set the record
position adjustment value to 20.
UA ZERO,1,20
Description • Check the recorded result and correct the
record position adjustment value.
• To end the adjustment, execute the UY0
command. If you do not end the adjustment,
you cannot change the execution mode.
• The unit for p3 is 1/30 mm.
4
RD100B: An integer
between 0 and 70
RD1800B: An integer
between 0 and 180
RD100B: An integer
between –45 to 15
(reference value:
3026)
RD1800B: An integer
between –165 to 165
(reference value:
5447)
4-23