Specifications; Lan; Digital Input; Digital Output - Moxa Technologies ioMirror E3210 User Manual

Table of Contents

Advertisement

ioMirror E3210 User's Manual

Specifications

LAN

Interface
Protocols
Protection
IP Address

Digital Input

Channels
I/O Mode
Dry Contact
Wet Contact
Isolation
Common Type

Digital Output

Channels
I/O Mode
On-state Voltage
Output Current Rating
Optical Isolation
Common Type
Protection

Alarm Port

Channels
On-state Voltage
Output Current Rating
Optical Isolation

Software

Utilities
Configuration
10/100BaseTx with MDI/MDIX, RJ45
DHCP, BootP, TCP, UDP, IP, ICMP, ARP, HTTP, SNTP, ioMirror
Modbus/TCP up to 3 sockets
1.5 KV magnetic isolation
Fixed, dynamic (DHCP)
Default 192.168.127.254
8 points, source type, dry contact or wet contact
Digital Input
Logic 0: close to GND
Logic 1: open
Logic 0: 0 to 3 VDC
Logic 1: 10 to 30 VDC (DI COM to DI)
3K VDC/2 KVrms
8 points/1 COM
8 points, sink type
Digital Output
24 VDC nominal
Max 200 mA per channel
2K VDC/2 KVrms
8 points/1 COM
Over voltage protection: +50 VDC
Over current limit: 600 mA (typical)
Over temperature shutdown: 160°C min
1 point, sink type
24 VDC nominal
Max 200 mA
3K VDC/2 KVrms
ioMirrorAdmin for Windows
Web browser, ioMirrorAdmin
1-5
Introduction

Advertisement

Table of Contents
loading