Chapter 5
Voltage Configuration
Eaton 5115 Rack-Mount UPS (500–1500 VA) User's Guide
Additional UPS Features
This section describes:
S
Changing the voltage configuration
S
Network transient protector
S
Load segments
The DIP switches on the UPS rear panel (see Figure 18) are used to
configure the output voltage and the input voltage range.
1.
Verify that the UPS is off and unplugged.
To turn off the UPS, press and hold the
and then unplug the UPS from the power outlet.
2.
Set the DIP switches according to the configurations in Table 1.
3.
Plug the UPS into a power outlet.
4.
To turn the UPS on, press and hold the
UPS beep (approximately two seconds).
UPS Rear Panel
ON
Figure 18. DIP Switches
S
164201449 Rev B www.eaton.com/powerquality
button for two seconds
button until you hear the
OFF
1
2
39