Functions for Wall Mounted / Floor Standing Type
FVXS Series
Ex: When the target temperature is 25°C (77°F)
Cooling → 23°C (73.4°F): Thermostat OFF → 22°C (71.6°F): Switch to heating
Heating → 26.5°C (79.7°F): Thermostat OFF → 27.5°C (81.5°F): Switch to cooling
2.5
Thermostat Control
Outline
Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Details
Thermostat OFF Conditions
The temperature difference is in the zone A.
Thermostat ON Conditions
The temperature difference returns to the zone C after being in the zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in the zone B.
Cooling
Heating
CTXS, FTXS Series
60
Target temperature – 2.0°C (–3.6°F)
= Thermostat OFF
Target temperature – 3.0°C (–5.4°F)
(Cooling: 10 minutes, Heating: 10 seconds)
Zone C
Zone C
–1.0°C (–1.8°F)
Zone B
Zone B
–2.0°C (–3.6°F)
Zone A
Zone A
Zone A
Zone A
2.0°C (3.6°F)
Zone B
Zone B
1.5°C (2.7°F)
Zone C
Zone C
Cooling Operation
Heating Operation
Room thermistor temperature – target temperature
ON
ON
–0.5°C (–0.9°F)
–1.5°C (–2.7°F)
OFF
OFF
Room thermistor temperature – target temperature
OFF
OFF
2.0°C (3.6°F)
1.0°C (1.8°F)
0.5°C (0.9°F)
ON
ON
SiUS122226E
Target temperature + 2.5°C (+4.5°F)
Target temperature + 1.5°C (+2.7°F)
= Thermostat OFF
(R22000)
(R24031)
(R24033)
Part 4 Functions and Control