Fan Speed Control For Indoor Units - Daikin FTKS20CVMB Service Manual

Inverter pair wall mounted type c-series
Hide thumbs Also See for FTKS20CVMB:
Table of Contents

Advertisement

SiBE04-401
1.3

Fan Speed Control for Indoor Units

Control Mode
The airflow rate can be automatically controlled depending on the difference between the set
temperature and the room temperature. This is done through phase control and Hall IC control.
For more information about Hall IC, refer to trouble shooting for fan motor on page 99.
Phase Steps
Phase control and fan speed control contains 9 steps: LLL, LL, SL, L, ML, M, MH, H and HH.
LLL (Heating thermostat OFF)
LL (Cooling thermostat OFF)
SL (Silent)
L
ML
M
MH
H
HH (Powerful)
Note:
1. During powerful operation, fan operate H tap + 50 - 90 rpm.
2. Fan stops during defrost operation.
Automatic Air
The following drawing explains the principle for fan speed control for heating:
Flow Control for
Heating
Automatic Air
The following drawing explains the principle of fan speed control for cooling:
Flow Control for
Cooling
Function and Control
Step
= Within this range the airflow rate is automatically controlled when the FAN setting
button is set to automatic.
Thermostat
setting
temperature
-0.5˚C
-1.5˚C
fan speed
fan speed
+1.5˚C
+0.5˚C
Thermostat
setting
temperature
Cooling
Heating
(R4085)
(R4085)
Phase control
L
-1˚C
ML
-2˚C
M
M
+2˚C
ML
+1˚C
L
Phase control
Main Functions
Dry mode
25 · 35kW class :
500 - 860 rpm
(During powerful operation :
850 - 910 rpm)
Difference between room
and set temperature
(R2819)
Difference between room
and set temperature
(R2820)
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents