3–12
"A" Group: Standard Functions
The inverter has other control sources that can temporarily override the parameter A001
setting, forcing a different output frequency source. The following table lists all
frequency source setting methods and their relative priority ("1" is the highest priority).
Priority
1
2
3
4
5
6
The inverter also has other control sources that can temporarily override the parameter
A002 setting, forcing a different Run command source. The following table lists all Run
command setting methods and their relative priority ("1" is the highest priority).
Priority
1
2
3
4
A001 Frequency Source Setting Method
[CF1] to [CF4] Multi-speed terminals
[OPE] Operator Control intelligent input
[F-TM] intelligent input
[AT] terminal
TM/PRG DIP Switch - (if switch is in "TM" position)
A001 Frequency source setting
A002 Run Command Setting Method
[OPE] Operator Control intelligent input
[F-TM] intelligent input
TM/PRG DIP Switch - (if switch is in "TM" position)
A002 Run command source setting
Refer to page...
4–13
4–31
4–33
4–23
3–11
3–10
Refer to page...
4–31
4–33
3–11
3–10