Overload Advance Notice Signal - Hitachi L2002 Instruction Manual

L2002 series
Hide thumbs Also See for L2002:
Table of Contents

Advertisement

Overload Advance Notice Signal

When the output current exceeds a preset
value, the [OL] terminal signal turns ON.
The parameter C041 sets the overload
threshold. The overload detection circuit
operates during powered motor opera-
tion and during regenerative braking. The
output circuits use open-collector
transistors, and are active low.
Option
Terminal
Code
Symbol
03
OL
Overload Advance
Notice Signal
11, 12, AL0 – AL2
Valid for outputs:
C041
Required settings:
Notes:
The default value is 100%. To change the level
from the default, set C041 (overload level).
The accuracy of this function is the same as the
function of the output current monitor on the [FM]
terminal (see
"Analog Output Operation" on
page
4–55).
The example circuit for terminal [12] drives a relay
coil. Note the use of a diode to prevent the negative-
going turn-off spike generated by the coil from
damaging the inverter's output transistor.
Output
Function Name
State
ON
OFF
L200
Current
C041
C041
[OL]
1
ON
Signal
0
Description
when output current is more than the set thresh-
old for the overload signal
when output current is less than the set threshold
for the overload signal
Example (requires output configuration—
see page 3–54):
Inverter output
terminal circuit
+
Example for terminals [AL0], [AL1], [AL2]
(requires output configuration—
4–36
see pages
and 3–54):
Inverter logic
circuit board
AL0
Power
See I/O specs
supply
on page 4–6.
4–41
Inverter
2
threshold
power running
regeneration
threshold
ON
t
OL
CM2
12 11
RY
OL
AL1
AL2
Load