Hitachi L2002 Instruction Manual page 192

L2002 series
Hide thumbs Also See for L2002:
Table of Contents

Advertisement

4–48
Using Intelligent Output Terminals
Option
Terminal
Code
Symbol
07
FBV
Valid for outputs:
Required settings:
Notes:
The [FBV] is designed for implementing two-stage
control. The PV high limit and PV low limit param-
eters, C052 and C053, do not function as process
alarm thresholds. Terminal [FBV] does not provide
a PID alarm function.
The example circuit for terminal [12] drives a relay
coil. Note the use of a diode to prevent the negative-
going turn-off spike generated by the coil from
damaging the inverter's output transistor.
Output
Function Name
State
Feedback Value
ON
Check
OFF
11, 12, AL0 – AL2
A076, C052, C053
Description
Transitions to ON when the inverter is in RUN
Mode and the PID Process Variable (PV) is
less than the Feedback Low Limit (C053)
Transitions to OFF when the PID Feedback
Value (PV) exceeds the PID High Limit
(C052)
Transitions to OFF when the inverter goes
from Run Mode to Stop Mode
Example (requires output configuration—
see page 3–54):
Inverter output
terminal circuit
Example for terminals [AL0], [AL1], [AL2]
(requires output configuration—
4–36
see pages
and 3–54):
Inverter logic
circuit board
AL0
Power
See I/O specs
supply
on page 4–6.
FBV
CM2
12 11
+
RY
FBV
AL1
AL2
Load