The following table lists the holding registers for the "C" Group Intelligent Input
I
Functions.
Func.
Name
Code
C001 Terminal [1] function
C002 Terminal [2] function
C003 Terminal [3] function
C004 Terminal [4] function
C005 Terminal [5] function
C011 Terminal [1] active state R/W Select logic convention, two
C012 Terminal [2] active state R/W
C013 Terminal [3] active state R/W
C014 Terminal [4] active state R/W
C015 Terminal [5] active state R/W
C021 Terminal [11] function
C022 Terminal [12] function
C026 Alarm relay terminal
function
C028 [AM] signal selection
C031 Terminal [11] active
state
C032 Terminal [12] active
state
C036 Alarm relay active state
"C" Group Intelligent Terminal Functions
R/W
Description
R/W
R/W
R/W
"Input Terminal
See
R/W
Configuration" on page 3–
R/W
47
option codes:
00...normally open [NO]
01...normally closed [NC]
R/W
"Output Terminal
See
R/W
Configuration" on page 3–
54
R/W
R/W Two available functions:
00...Actual motor speed
01...Motor current
R/W Select logic convention, two
option codes:
00...normally open (NO)
01...normally closed (NC)
R/W Select logic convention, two
option codes:
00...normally open (NO)
01...normally closed (NC)
R/W Select logic convention, two
option codes:
00...normally open (NO)
01...normally closed (NC)
L200
Inverter
2
Network Data
Register
Range
hex
dec.
1103h 04355 0, 1, 2, 3,
4, 5, 6, 7,
1104h 04356
8, 9, 11,
12, 13,
1105h 04357
15, 16,
1106h 04358
18, 19,
20, 21,
1107h 04359
22, 23,
24, 27,
28, 29,
31, 50,
51, 255
110Bh 04363
0, 1
110Ch 04364
0, 1
110Dh 04365
0, 1
110Eh 04366
0, 1
110Fh 04367
0, 1
1114h 04372
0, 1, 2, 3,
1115h 04373
4, 5, 6, 7,
8, 9
1119h 04377
111Bh 04379
0, 1
111Dh 04381
0, 1
111Eh 04382
0, 1
1122h 04370
0, 1
B–39