Hitachi L2002 Instruction Manual page 170

L2002 series
Hide thumbs Also See for L2002:
Table of Contents

Advertisement

4–26
Using Intelligent Input Terminals
Three-wire Interface Operation
The 3-wire interface is an industry standard motor control interface. This function uses
two inputs for momentary contact start/stop control, and a third for selecting forward or
reverse direction. To implement the 3-wire interface, assign 20 [STA] (Start), 21 [STP]
(Stop), and 22 [F/R] (Forward/Reverse) to three of the intelligent input terminals. Use a
momentary contact for Start and Stop. Use a selector switch, such as SPST for the
Forward/Reverse input. Be sure to set the operation command selection A002=01 for
input terminal control of motor.
If you have a motor control interface that needs logic-level control (rather than momen-
tary pulse control), use the [FW] and [RV] inputs instead.
Option
Terminal
Code
Symbol
20
STA
21
STP
22
F/R
Valid for inputs:
Required settings:
Notes:
The STP logic is inverted. Normally the switch will
be closed, so you open the switch to stop. In this
way, a broken wire causes the motor to stop
automatically (safe design).
When you configure the inverter for 3-wire inter-
face control, the dedicated [FW] terminal is
automatically disabled. The [RV] intelligent
terminal assignment is also disabled.
Input
Function Name
State
Start Motor
ON
OFF
Stop Motor
ON
OFF
Forward/Reverse
ON
OFF
C001, C002, C003, C004,
C005
A002 = 01
Description
Start motor rotation on momentary contact (uses
acceleration profile)
No change to motor operation
No change to motor operation
Stop motor rotation on momentary contact (uses
deceleration profile)
Select reverse direction of rotation
Select forward direction of rotation
Example (requires input configuration—
see page 3–47):
STP
F/R
STA
L
5
4
See I/O specs on page 4–6.
3
2
1
PCS