Hitachi L2002 Instruction Manual page 15

L2002 series
Hide thumbs Also See for L2002:
Table of Contents

Advertisement

Terminal Tightening Torque and Wire Size
The wire size range and tightening torque for field wiring terminals are presented in the
tables below.
Motor Output
Input
Voltage
kW
0.2
0.4
0.55
0.75
1.1
200V
1.5
2.2
3.7
5.5
7.5
0.4
0.75
1.5
2.2
400V
3.0
4.0
5.5
7.5
Terminal Connector
Logic/Analog connector
Relay connector
Wire Connectors
WARNING: Field wiring connections must be
made by a UL Listed and CSA Certified ring lug
terminal connector sized for the wire gauge being
used. The connector must be fixed using the
crimping tool specified by the connector
manufacturer.
Inverter Model
HP
1/4
L200-002NFE(F)2/NFU2
1/2
L200-004NFE(F)2/NFU2
3/4
L200-005NFE(F)2
1
L200-007NFE(F)2/NFU2
1 1/2
L200-011NFE(F)2
2
L200-015NFE(F)2/NFU2
3
L200-022NFE(F)2/NFU2
5
L200-037LFU2
7 1/2
L200-055LFU2
10
L200-075LFU2
1/2
L200-004HFE(F)2/HFU2
1
L200-007HFE(F)2/HFU2
2
L200-015HFE(F)2/HFU2
3
L200-022HFE(F)2/HFU2
4
L200-030HFE(F)2
5
L200-040HFE(F)2/HFU2
7 1/2
L200-055HFE(F)2/HFU2
10
L200-075HFE(F)2/HFU2
Wiring Size
Range (AWG)
30—16
30—14
L200
Inverter
2
Power Terminal
Wiring Size
ft-lbs
Range (AWG)
16
0.6
14
12
0.9
10
12
10
1.5
8
16
0.9
14
12
1.5
Torque
ft-lbs
(N-m)
0.16—0.19 0.22—0.25
0.37—0.44
0.5—0.6
Terminal (ring lug)
xiii
Torque
(N-m)
0.8
1.2
2.0
1.2
2.0
Cable support
Cable

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents