Pr.
Pr.
65, 67 to 69

Retry function at alarm occurrence

Pr.65 Retry selection
Pr.68 Retry waiting time
If an alarm occurs, the inverter resets itself automatically to restart.
You can also select the alarm description for a retry.
When automatic restart after instantaneous power failure is
selected (Pr.57 Restart coasting time
performed at retry operation as at an instantaneous power failure.
Use Pr.65 to select the alarm to be activated for retries.
indicates the alarms selected for retry.
" "
Alarm
Indication for
0
Retry
E.OC1
E.OC2
E.OC3
E.OV1
E.OV2
E.OV3
E.THM
E.THT
E.IPF
E.UVT
E. BE
E. GF
E.OHT
E.OLT
E.OPT
E.OP1
E.OP2
E.OP3
E. PE
E.MB1
E.MB2
E.MB3
E.MB4
E.MB5
E.MB6
E.MB7
E.OS
E.OSD
E.OD
E.PTC
E.CDO
E.SER
E.ILF
Set the number of retries at alarm occurrence in Pr.67.
Pr.67 Setting
0 (initial value)
1 to 10
101 to 110
Use Pr.68 to set the waiting time from when an inverter alarm occurs
until a retry is made in the range 0 to 10s.
Reading the Pr.69 value provides the cumulative number of
successful restart times made by retry.
Pr.
Pr.
66
Refer to the section about Pr. 22.
Pr.
Pr.
67 to 69
Refer to the section about Pr. 65.
Pr.
Pr.
70
Refer to the section about Pr. 30.
51
When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.67 Number of retries at alarm occurrence
Pr.69 Retry count display erase
9999), restart operation is
Pr.65 Setting
1
2
3
4
Description
No retry function
Set the number of retries at alarm occurrence.
An alarm output is not provided during retry
operation.
Set the number of retries at alarm occurrence. (The
setting value of minus 100 is the number of retries.)
An alarm output is provided during retry operation.
Pr.
Pr.
71, 450

Motor selection (applied motor)

Pr.71 Applied motor
Setting of the used motor selects the thermal characteristic appropriate
for the motor.
Setting is necessary when using a constant-torque motor. Thermal
characteristic of the electronic thermal relay function suitable for
the motor is set.
Pr.71,
Thermal Characteristic of the
Pr.450
Electronic Thermal Relay
Setting
Function
Thermal characteristics of a standard motor
0
(Pr. 71 initial value)
5
Thermal characteristics of the
1
Mitsubishi constant-torque motor
Thermal characteristics of a standard motor
2
Adjustable 5 points V/F
Mitsubishi standard motor SF-JR4P
20
(1.5kW or less) thermal characteristic
for the constant-torque motor
Thermal characteristics of the
30
Mitsubishi vector motor SF-V5RU
Thermal characteristic of Mitsubishi
40
standard motor SF-HR
Thermal characteristic of Mitsubishi
50
constant-torque motor SF-HRCA
3
Standard
13
Constant-torque
Mitsubishi standard
23
SF-JR4P (1.5kW or less)
Mitsubishi vector
33
SF-V5RU/SF-THY
Mitsubishi high
43
efficiency SF-HR
Mitsubishi constant-
53
torque SF-HRCA
4
Standard
14
Constant-torque
Mitsubishi standard
24
SF-JR4P (1.5kW or less)
Mitsubishi vector
34
SF-V5RU/SF-THY
Mitsubishi high
44
efficiency SF-HR
Mitsubishi constant-
54
torque SF-HRCA
5
Standard *3
15
Constant-torque *3
6
Standard *4
16
Constant-torque *4
7
Standard *3
17
Constant-torque *3
8
Standard *4
18
Constant-torque *4
9999
Function invalid (only Pr.450 can be set, initial value)
*1
Motor constants of Mitsubishi high efficiency motor SF-HR
*2
Motor constants of Mitsubishi constant-torque motor SF-HRCA.
*3
Star connection
*4
Delta connection
For the 5.5K and 7.5K, the Pr. 0 Torque boost and Pr. 12 DC injection
brake operation voltage settings are automatically changed according
to the Pr. 71 and Pr.450 settings as follows.
Pr.71
Standard Motor Setting
Pr.450
0, 2, 3 to 8, 20, 23, 24, 40, 43, 44
Pr.0
Pr.12
Pr.450 Second applied motor
Motor
( : Motor used)
Constant
Standard
torque
(SF-JR,
(SF-JRCA,
etc.)
etc.)
*1
*2
Select "offline
auto tuning
setting"
*1
*2
Auto tuning data
can be read,
changed, and set
*1
*2
Direct input of
motor constants
is enabled
Motor constants
direct input
+
offline auto
tuning
Constant-Torque Motor
Setting
1, 13 to 18, 50, 53, 54
3%
2%
4%
2%
Vector
(SF-V5RU,
etc.)