Terminal Connection Diagram - Mitsubishi Electric FR-A700 Manual

Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Terminal Connection Diagram

Sink logic
*1. DC reactor (FR-HEL)
Be sure to connect the DC reactor
Main circuit terminal
supplied with the 75K or more.
Control circuit terminal
When a DC reactor is connected to
the 55K or less, remove the jumper
across P1-P/+.
Three-phase AC
power supply
*2. To supply power to the
control circuit separately,
remove the jumper across
R1/L11 and S1/L21.
Control input signals (No voltage input allowed)
Terminal functions vary with
the input terminal
assignment (Pr. 178 to Pr. 189)
(Refer to the Instruction
Manual (applied))
holding selection
Multi-speed
selection
*3. JOG terminal can be used
as pulse train input terminal.
Use Pr.291 to select
JOG/pulse.
Second function selection
*4. AU terminal can be
used as PTC input
terminal.
Terminal 4 input selection
(Current input selection)
Selection of automatic restart
after instantaneous
power failure
Contact input common
(Common for external power supply transistor)
Frequency setting signal (Analog)
Frequency setting
potentiometer
1/2W1k Ω
*6
(+)
Auxiliary input
(-)
Terminal 4 input
(+)
(Current input)
(-)
* 5. Terminal input specifications can
be changed by analog input
specifications switchover (Pr. 73,
Pr. 267) .
*6 . It is recommended to use 2W1kΩ
when the frequency setting signal
is changed frequently.
CAUTION
To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables.
Be sure to earth (ground) the inverter and motor before use.
This connection diagram assumes that the control circuit is sink logic (initial setting). Refer to the instruction manual for the connection in the case of
source logic.
Earth
(Ground)
MCCB
MC
R/L1
S/L2
T/L3
R1/L11
Jumper
S1/L21
*2
Earth
(Ground)
Forward
STF
rotation
start
STR
Reverse
rotation
start
STOP
Start self-
RH
High speed
RM
Middle
speed
RL
Low speed
JOG
Jog mode
RT
MRS
Output stop
RES
Reset
AU
CS
SD
PC
24VDC power supply
10E(+10V)
10(+5V)
3
0 to 5VDC
2
2
0 to 10VDC
4 to 20mADC
5
1
(Analog common)
0 to ± 10VDC
1
0 to ± 5VDC
4 to 20mADC
4
0 to 5VDC
0 to 10VDC
Connector
Option connector 1
for plug-in option
connection
Option connector 2
Option connector 3
Brake unit
*1
(Option)
R
*8
Jumper
Jumper
Jumper
CN8
P1
P/+
PX
PR
N/-
*7
R
U
V
ON
EMC filter
W
ON/OFF
OFF
connecter
*9
Main circuit
Control circuit
C1
B1
A1
C2
B2
A2
RUN
*3
SU
IPF
*4
OL
AU
FU
PTC
SE
PU
connector
USB
FM
connector
*11
(Initial value)
SD
selected
*5
AM
5
(Initial value)
selected
*5
TXD+
(Initial value)
TXD-
*5
selected
RXD+
RXD-
SG
Terminating
VCC
resistor
*7. A CN8 connector is provided with the 75K
or more.
*8. Brake resistor (FR-ABR)
Remove the jumper across terminal PR-PX
when connecting a brake resistor.
(0.4K to 7.5K)
Terminal PR is provided for the 0.4K to 22K.
Install a thermal relay to prevent an overheat
and burnout of the brake resistor.
(Refer to the Instruction Manual)
Motor
IM
Earth (Ground)
*9.The FR-A720-0.4K and 0.75K
are not provided with the EMC
filter ON/OFF connector. (Always on)
Relay output
Terminal functions
Relay output 1
vary with the output
(Alarm output)
terminal assignment
(Pr. 195, Pr. 196)
(Refer to the
Instruction Manual
(applied))
Relay output 2
Open collector output
Running
Terminal functions
vary with the output
Up to frequency
terminal assignment
(Pr. 190 to Pr. 194)
Instantaneous
power failure
(Refer to the
Instruction Manual
Overload
(applied))
Frequency detection
Open collector output common
Sink / source common
* 10. It is not necessary
*11. FM terminal can
be used for pulse
when calibrating the
train output of open
indicator from the
collector output
operation panel.
using Pr.291.
+
-
Indicator
(Frequency meter, etc.)
Calibration
Moving-coil type
resistor * 10
1mA full-scale
(+)
Analog signal output
(0 to 10VDC)
(-)
RS-485 terminals
Data transmission
Data reception
GND
(Permissible load
5V
current 100mA)
22