11.6 TROUBLESHOOTING E-MAIL NOTIFICATION (SMTP)

When e-mail notification via SMTP is configured and enabled, the SNMP/Web adapter will notify the
selected recipients upon UPS alarm activation / deactivation. If problems are experienced with this
functionality, follow the flowchart below to identify the root-cause of the problem and implement proper
corrective actions.
Please note that proper configuration of the SNMP/Web adapter and the SMTP server set-up and
configuration are responsibility of the user. This section aims to give basic troubleshooting guidance.
For details on SMTP protocol refer to RFC 821, RFC 1123 and RFC 2821.
E-mail notification
E-mail notification
E-mail OK
E-mail OK
Check SMTP server operation
Check SMTP server operation
telnet my.smtp.server smtp
telnet my.smtp.server smtp
Server OK ?
Server OK ?
Ping SMTP server
Ping SMTP server
from the adapter
from the adapter
Ping OK ?
Ping OK ?
Send test e-mail
Send test e-mail
GEDE>sendemail test
GEDE>sendemail test
Y
Y
OK
OK
Email OK ?
Email OK ?
(*)If the adapter and the SMTP server belong to different subnets check the gateway settings.
(**) Particularly:
If the SMTP server supports logging, enable the log functionality. Server error messages may
give useful hints on the nature of the problem
Check the SNMP/Web adapter hostname (must be a valid domain name), SMTP sender-name
and e-mail recipient (both must be valid e-mail addresses)
If the SMTP server requires authentication, verify the account settings on the SNMP/Web
adapter.
With reference to Authentication, the embedded e-mail client only supports the CRAM-MD5 and LOGIN
mechanisms. Make sure the e-mail server supports at least one of these mechanisms.
Modifications reserved
OPM_CNT_SNM_BAS_CRD_1GB_V014.doc
Y
Y
OK
OK
N
N
Y
Y
Resolve SMTP
Resolve SMTP
server issues
server issues
N
N
N
N
Verify TCP/IP settings
Verify TCP/IP settings
(*)
(*)
Y
Y
Check adapter /
Check adapter /
N
N
SNMP server
SNMP server
configuration (**)
configuration (**)
Page 67/69