Ge Mib Objects - GE Digital Energy 1018959 Operating Manual

Digital energy snmp / web adapter
Hide thumbs Also See for Digital Energy 1018959:
Table of Contents

Advertisement

4.3

GE MIB OBJECTS

GE provides private MIBs, which enhance the UPS information available over SNMP interface.
These MIBs are only supported on 3-ph SNMP/Web plug-in adapter.
Two different version of the GE private MIB exist:
GE Single MIB: to be used for monitoring of a 3-ph UPS is single unit configuration
GE Parallel MIB: to be used for monitoring of a 3-ph parallel UPS system
The MIB structure is shown in the following picture. The geGenericUPS group provides information on
the unit in stand-alone configuration or on the overall system in a parallel configuration. The geFirstUPS
... geEightUPS groups provide information on the units that are part of a parallel configuration.
geUPS (1.3.6.1.4.1.818.1.1)
geUPS (1.3.6.1.4.1.818.1.1)
geGenericUPS(10)
geGenericUPS(10)
geFirstUPS(11)
geFirstUPS(11)
geSecondUPS(12)
geSecondUPS(12)
geEigthUPS(18)
geEigthUPS(18)
For each of these groups the 3-ph SNMP/Web plug-in adapter supports the following objects.
(Objects marked with [*] do not have a RFC1628 correspondence)
OIDs
==== upsIdent Group ====
upsIdentManufacturer
upsIdentModel
upsIdentUPSSoftwareVersion
upsIdentAgentSoftwareVersion
upsIdentName
upsIdentAttachedDevices
upsIdentsUPSSerialNumber [*]
upsIdentComProtVersion [*]
upsIdentOperatingTime [*]
==== uspBattery Group ====
upsBatteryStatus
upsSecondsOnBattery
upsEstimatedMinutesRemaining
upsEstimatedChargeRemaining
upsBatteryVoltage
upsBatteryCurrent
upsBatteryTemperature
upsBatteryRipple [*]
==== upsInput Group ====
upsInputLineBads
upsInputNumLines
upsInputFrequency
Modifications reserved
OPM_CNT_SNM_BAS_CRD_1GB_V014.doc
Parallel
Parallel
system
system
only
only
...
...
TRAPS & ALARMS
==== geUPSTraps & upsWellKnownAlarms group
====
upsAlarmBatteryBad
upsAlarmOnBattery
upsAlarmLowBattery
upsAlarmDepletedBattery
upsAlarmTempBad
upsAlarmInputBad
upsAlarmOutputBad
upsAlarmOutputOverload
upsAlarmOnBypass
upsAlarmBypassBad
upsAlarmOutputOffAsRequested
upsAlarmUpsOffAsRequested
upsAlarmChargerFailed
upsAlarmUpsOutputOff
upsAlarmUpsSystemOff
upsAlarmFanFailure
upsAlarmFuseFailure
upsAlarmGeneralFault
upsAlarmDiagnosticTestFailed
upsAlarmCommunicationsLost
upsAlarmAwaitingPower
upsAlarmShutdownPending
upsAlarmShutdownImminent