3.6

SNMP SECTION

The SNMP section deals with SNMP and trap configuration.

3.6.1 SNMP settings page

The most relevant SNMP settings are the following:
Parameter Name
Port Number
Get Community
Set Community

3.6.2 Trap settings page

This page allows to configure up to 20 recipients of SNMP traps. The most relevant settings are the
following:
Parameter Name
Trap destination
Community
V2
Port

3.6.3 Alarm notification page

This page is used to configure the alarm notification via trap and/or e-mail. Every alarm is listed, and the
user may enable the notification via trap and/or e-mail upon alarm (de)activation.
Further to this, alarm handling can be enabled/disabled through the Enable checkbox. When disabled,
an alarm occurrence is totally filtered – the alarm will never appear active, it will not be reported by any
mean and it will not be logged.
Modifications reserved
OPM_CNT_SNM_BAS_CRD_1GB_V014.doc
Description
Set SNMP server listening port. Default port is 161.
Defines the community name for receiving SNMP information (GET). The get
community name controls access to the SNMP Agent – the community in the
request
must
The default value is public.
Defines the community name for writing SNMP information (SET). The set
community name controls access to the SNMP Agent – the community in the
request must match the setcommunity parameter. The default value is private.
Description
IP-address of the trap target
Community name (optional – default is public)
Controls SNMP trap version:
If unchecked, v1 traps are sent (default)
If checked, V2 traps are sent
Port to which the trap will be sent (optional – default 162)
match
the
getcommunity
parameter.