SNMP AGENT

The SNMP/Web adapters implement an SNMP Agent providing access to OIDs according to the MIB
structure, and may generate traps at the occurrence of specific events. This allows one or more NMSs
(Network Management Systems) to monitor, manage and control the UPS.
The SNMP Agent complies with the standard UPS-MIB as specified in RFC1628. Limited to the 3-ph
SNMP/Web plug-in adapter, additional information is available with the GESingle and GEParallel MIBs.
The SNMP/Web adapter implements both SNMP v1 and SNMP v2 protocols. Always remember that with
these protocols the information travel on the network in plain text. It is therefore recommended to
disable the SNMP Agent when this functionality is not used. Refer to the "Security" section of this manual
for further details.
4.1

MIB STRUCTURE

iso(1).org(3).dod(6).internet(1)
iso(1).org(3).dod(6).internet(1)
RFC1628 MIB is available in the upsMIB group.
Additional UPS information is available in the GE MIB under the geUPS group (limited to the 3-ph
SNMP/Web plug-in adapter).
4.2

RFC1628 MIB OBJECTS

The SNMP/Web adapters support the following RFC1628 Objects:
OIDs
==== upsIdent Group ====
upsIdentManufacturer
upsIdentModel
upsIdentUPSSoftwareVersion
upsIdentAgentSoftwareVersion
upsIdentName
upsIdentAttachedDevices
==== uspBattery Group ====
upsBatteryStatus
upsSecondsOnBattery
upsEstimatedMinutesRemaining
upsEstimatedChargeRemaining
upsBatteryVoltage
upsBatteryCurrent
upsBatteryTemperature
Modifications reserved
OPM_CNT_SNM_BAS_CRD_1GB_V014.doc
mgmt(2)
mgmt(2)
mib-2(1)
mib-2(1)
upsMIB(33)
upsMIB(33)
private(4)
private(4)
enterprises(1)
enterprises(1)
imv(818)
imv(818)
geHardware(1)
geHardware(1)
geUPS(1)
geUPS(1)
TRAPS & ALARMS
==== upsTrap Group ====
UpsTrapOnBattery
UpsTrapTestCompleted
UpsTrapAlarmEntryAdded
UpsTrapAlarmEntryRemoved
==== upsWellKnownAlarms group ====
UpsAlarmBatteryBad
UpsAlarmOnBattery
UpsAlarmLowBattery
UpsAlarmDepletedBattery
UpsAlarmTempBad
UpsAlarmInputBad
UpsAlarmOutputBad
UpsAlarmOutputOverload
UpsAlarmOnBypass