Rev 2.4
Figure 8: Which Side of the Rack Do You Want the Connectors?
The distance between the rack and the door can be as little as 4 cm on one side
of the rack and as much as 18 cm on the other side of the rack. Keep in mind that
there can be as many as 36 cables connected to the switch.
• Do you want the connector side recessed in the rack to allow for larger cable bending radius?
• Will the connector side be recessed past other equipment in the rack and will this be problem-
atic?
3. Install the rail slides onto the switch. Place the end of the rail slide with the 90
of the switch that you want to be even with the vertical support of the 19" rack. Use four of the
flat head screws for each rail slide. There are two sets of holes in the rail slide. Select the set of
holes to either mount the switch closer or farther away from the rack vertical support. Tighten
the screws to 3Nm or 26.5 pound inches.
This side of the
switch will be
next to the ver-
20
Mellanox Technologies
Figure 9: Screwing the Rail Slide onto the switch
Installation and Basic Operation
o
angle on the side

Advertisement