Approved Configurations With No Elbows Or Two 45¡ Offsets (Vertical Termination) - Travis Industries DVS FIREPLACE Owner's Manual

Built-in direct vent fireplace
Hide thumbs Also See for DVS FIREPLACE:
Table of Contents

Advertisement

I
NSTALLATION
P
18
AGE
Approved Venting Configurations for
Vertical Terminations with or without
Offsets
¥
11 Foot Minimum System Height (with or
without offsets)
¥
35 Foot Maximum System Height
¥
8' 7" Maximum Offset
¥
A Maximum of Two 45¡ Elbows May be
Used
¥
The termination must fall within the shaded
area shown in the chart. Use the indicated
restrictor position.
Vertical
Rise
Offset Length
None
1' Section
2' Section
3' Section
4' Section
4' + 1' Section
4' + 2' Section
4' + 3' Section
4' + 4' Section
(C
ONT
Horizontal
Offset
Offset
Length
Hor. Offset
Vert. Rise
5"
1'
1' 7"
1' 9"
2' 4"
2' 5"
3' 2"
3' 8"
3' 9"
4' 4"
4' 6"
5' 2"
5' 9"
6'
6' 9"
.)
- For Qualified Installers Only!
35' (max.)
30 feet
25 feet
20 feet
15 feet
11' (min.)
1'
3'
5 feet
5'
0 feet
Restrictor
Position # 3
The maximum offset
length is three 4'
sections.
35' (max.)
30 feet
25 feet
20 feet
15 feet
11' (min.)
5 feet
0 feet