Side Vent Configuration with Horizontal Termination (no vertical rise)

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and diffuser
positions.
HINT: Travis Industries provides a minmum vent kit (sku 98900168). It includes a 4" (102mm) section and a
horizontal termination cap.
3 feet (0.915m)
© Travis Industries
Installation
(for qualified installers only)
Optional 45° Elbow
Vent with No 45° Elbow
0 feet
Vent with 1 45° Elbow
3 feet (0.915m)
0 feet
4090507
See the charts below to
determine maximum vent
Termination
• Exhaust Restrictor # 1 (stock)
• Intake Restrictor # 1 (stock)
• Diffuser Position # 1
• Min. 4" (102mm) Horizontal Section
• Max.48" (1219mm) Horizontal
Section(s)
• Exhaust Restrictor # 1 (stock)
• Intake Restrictor # 1 (stock)
• Diffuser Position # 1
• Min. 4" (102mm) Horizontal Section
• Max. 24" (610mm) Horizontal
Section(s)