Rear Vent Configuration with Horizontal Termination (no vertical rise)

The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and
diffuser positions.
Vent with No 45° Elbow
3 feet (0.915m)
Vent with 1 45° Elbow
3 feet (0.915m)
Travis Industries
Installation
See the charts below to
determine maximum vent
Optional 45° Elbow
0 feet
0 feet
(for qualified installers only)
Termination
• Exhaust Restrictor # 1 (stock)
• Intake Restrictor # 1 (stock)
• Diffuser Position # 1 (stock)
• Min. 4" (102mm) Horizontal Section
• Max.48" (1219mm) Horizontal
Section(s)
• Exhaust Restrictor # 1 (stock)
• Intake Restrictor # 1 (stock)
• Diffuser Position # 1 (stock)
• Min. 4" (102mm) Horizontal Section
• Max. 24" (610mm) Horizontal
Section(s)