Figure 63: Parameter Cnfg Ctl Clg It

CLG IT: Displays and allows modification of cooling
PID control integral time. Its value ranges from 0 to
5000 sec.
Integral Time (IT):
When TR is nonzero, this value of IT is used by the
space cooling PID control.
Auto Gain Selection:
When TR is 0,
Table 6
shows the IT values are used
by the space cooling PID control.
Table 6: IT values used by the space cooling pid
control.
Without
Type
Economizer IT
1stg
3333
2stg
2000
3stg
1429
4stg
1111
With
Economizer IT
2000
1429
1111
909
36

Figure 64: Parameter Cnfg Ctl Htg Type

HTG TYPE: Displays and allows modification of
heating output type for conventional or heat pump
auxiliary heat as: NONE, 1STG, 2STG, 3STG, 4STG,
ANA.
Default configuration: 2STG
Configuration settings in program are as follows:
0 = NONE, 1 = 1STG, 2 = 2STG, 3 = 3STG,
4 = 4STG, 10 = ANA
Note:
1. Modulating heating is not supported for
heat pump auxiliary heat.
2. Automatic Gain Selection feature is
enabled when Throttling Range (TR) is 0.
Default TR is 0