Cnfg Ui
(Configuration of CVAHU universal inputs)
Figure 69: Parameter Cnfg Ui Ui 1
UI 1: Displays and allows modification of input type
for universal input 1. This can be changed as: NTC,
TR T, TRAB, TRRL, DGNO, and DGNC.
Default configuration: NTC
Configuration settings in program are as follows:
0 = NTC (20 KNTC)
1 = TR T (TR2x 20KNTC)
2 = TRAB (TR2x Setpoint Absolute)
3 = TRRL (TR2x Setpoint Relative)
14 = DGNO (Digital Normally Open)
15 = DGNC (Digital Normally Closed)
Clicking NEXT the following parameters are available
with configuration settings similar to UI1:
UI2 = Universal Input2
UI3 = Universal Input3
UI4 = Universal Input4
UI5 = Universal Input5
UI6 = Universal Input6
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Cnfg Di
(Configuration of CVAHU digital inputs)
Figure 70: Parameter Cnfg Di Di 1
DI 1: Displays and allows modification of input type
for digital input 1. This can be changed as: DGNO,
DGNC, and UNDEFINED.
Default configuration: UNDEFINED
Configuration settings in program are as follows:
14 = DGNO (Digital Normally Open)
15 = DGNC (Digital Normally Closed)
255 = UNDEFINED
Clicking NEXT the following parameters are available
with configuration settings similar to DI1:
DI2 = Digital Input2
DI3 = Digital Input3
DI4 = Digital Input4
39