Sensors; Figure 16: Parameters Sensors Zio Temp - Honeywell CUL6438SR-CV1 Configuration Manual

The controllers are free topology transceiver
Table of Contents

Advertisement

Sensors

(CVAHU sensor value display)
Click the PARAMETERS soft key to display the first
configured category 'SENSORS'. Within this
category, one sample Zio display is shown for
reference and the remaining parameters are available
for view only as per the following order.
Following is the path to access the screen as shown
in
Figure
16:
CONTRACTOR>PARAMETERS>SENSORS>ZIO
TEMP

Figure 16: Parameters Sensors Zio Temp

Click CANCEL to return to SENSORS. SENSOR
is parameter group for this parameter.
Click NEXT to access parameters in the following
sequence.
ZIO TEMP: Display Zio temperature which
corresponds to the onboard temperature sensor and
is an output of the Sbus wall module function block.
ZIO HUMIDITY: Displays Zio humidity (%) sensor
from wall module
ROOMTEMP: Displays room temperature and is an
input to the Sbus wall module function block.
RH: Displays room relative humidity (%) and is an
input to the Sbus wall module function block.
(PPM)
CO
: Displays room CO
2
2
Sbus wall module function block.
and is an input to the
21
STRYKER CVAHU ZIO CONFIGURATION GUIDE
DISCHRG: Displays discharge air temperature and is
an input to the Sbus wall module function block.
OAT: Displays outside air temperature and is an input
to the Sbus wall module function block.
OAH: Displays outside air humidity (%) and is an
input to the Sbus wall module function block.
OCC SNSR: Displays occupancy sensor and is an
input to the Sbus wall module function block.
Status is displayed as follows
OCC, UNOC, BYPS, STBY, UNDEFINED
Configuration settings in program are as follows:
0 = OCC (Occupancy Mode)
1 = UNOC (UN occupancy Mode)
2 = BYPS (Bypass Mode
3 = STBY (Standby Mode)
4 = UNDEFINED
WINDOW: Displays window open/closed contact
status and is an input to the Sbus wall module
function block.
Status is displayed as follows:
CLOS, OPEN, UNDEFINED
Configuration settings in program are as follows:
0 = CLOS (Window close status)
1 = OPEN (Window open status)
2 = UNDEFINED
MON SWTH: Displays monitory switch and is an input
to the Sbus wall module function block.
Status is displayed as follows:
OFF, ON, UNDEFINED
Configuration settings in program are as follows:
0 = OFF
1 = ON
255 = UNDEFINED
MON MODU: Displays mon modulation and is an
input to the Sbus wall module function block.