STRYKER CVAHU ZIO CONFIGURATION GUIDE

Override

(CVAHU override used for fan)

Figure 35: Parameter Override Fan Ovrd

FAN OVRD: Displays and allows modification of
supply fan override command as ON, OFF or
UNDEFINED.
Default configuration: UNDEFINED
Configuration settings in program are as follows:
0 = OFF, 1 = ON, 255 = UNDEFINED

Alarms

(CVAHU parameter alarms)

Figure 36: Parameter Alarms Emrg Ovrd

EMRG OVRD: Displays smoke detector status as
TRUE, FALS or UNDEFINED.
Configuration settings in program are as follows:
0 = FALS, 1 = TRUE, 255 = UNDEFINED

Figure 37: Parameter Alarms Clg Ovrd

CLG OVRD: Displays cooling override status as
TRUE, FALS or UNDEFINED.
Configuration settings in program are as follows:
0 = FALS, 1 = TRUE, 255 = UNDEFINED