Snsr Calibration
(CVAHU sensor calibration)
Figure 44: Parameter Snsr Cal Zio T Of
ZIO T OF: Displays and allows modification of Zio
temperature offset. Its value ranges from –100 to
+100.
Figure 45: Parameter Snsr Cal Zio H Of
ZIO H OF: Displays and allows modification of Zio
humidity (%) offset. Its value ranges from –100 to
+100.
STRYKER CVAHU ZIO CONFIGURATION GUIDE
Wm Config
(CVAHU wall module configuration)
Figure 46: Parameter Wm Config Units
UNITS: Displays and allows modification of units to
be displayed for temperature parameters as C, F,
UNDEFINED.
Default configuration: UNDEFINED
Configuration settings in program are as follows:
0 = F (Deg. F), 1 = C (Deg. C), 255 = UNDEFINED
Figure 47: Parameter Wm Config Type
TYPE: Displays and allows modification of type for
wall module to be used as NONE, TR20, ZIO,
UNDEFINED.
Default configuration: UNDEFINED
Configuration settings in program are as follows:
0 = NONE (No wall module)
1 = TR20 (Conventional wall module TR20)
2 = ZIO (ZIO TR71/TR75)
255 = UNDEFINED
31