Appendix 1 Technical Data

Parameter
category
Operating temperature
Storage temperature
Relative humidity
Environmental
Altitude
Pollution level
Others
Input phase voltage
Input voltage range
Input frequency
AC input
Max input current
Power factor
Over-voltage level
Rated output voltage
Output voltage range
Output current
DC output
Total regulation
Efficiency
Noise (peak-peak)
Weighted noise
AC input over-voltage
alarm point
AC input over-voltage
alarm recovery point
AC input under-voltage
alarm point
AC input under-voltage
AC input
alarm recovery point
alarm and
AC input over-voltage
protection
protection point
AC input over-voltage
protection recovery point
AC input under-voltage
protection point
AC input under-voltage
protection recovery point
DC output over-voltage
alarm point
DC output over-voltage
alarm recovery point
DC output
alarm and
DC output under-voltage
protection
alarm point
DC output under-voltage
alarm recovery point
BLVD point
Current sharing
Rectifier
Derate by input (45°C)
Appendix 1 Technical Data
Table 1 Technical data
Parameter
-5°C ~ 40°C
-40°C ~ 70°C
≤ 90%RH
≤ 2000m (derating is necessary above 2000m)
Level 2
No conductive dust or erosive gases. No danger of explosion
220Vac
90Vac ~ 290Vac
45Hz ~ 65Hz
Single phase, input current of each rectifier ≤ 7A
≥ 0.99
Level 2
-53.5Vdc
-42.3Vdc ~ -57.6Vdc
80A
≤ ±1%
≥ 90%
≤ 200mV
≤ 2mV
Default: 280Vac ± 10Vac, cofigurable through monitoring module
15Vac lower than the AC input over-voltage alarm point
Default: 180Vac ± 10Vac, configurable through monitoring module
15Vac higher than the AC input under-voltage alarm point
Default: 305Vac ± 5Vac
10Vac lower than the AC input over-voltage protection point
Default: 80Vac ± 5Vac
15Vac higher than the AC input under-voltage protection point
Default: 57.6Vdc ± 0.2Vdc, configurable through monitoring module
0.5Vdc lower than the over-voltage alarm point
Default: 45.0Vdc ± 0.2Vdc, configurable through monitoring module
0.5Vdc higher than the under-voltage alarm point
Default: 43.2Vdc ± 0.2Vdc, configurable through monitoring module
The imbalance is better than ± 5% rated output current. Test current range: 10% ~
100% rated current.
The imbalance is better than ± 3% rated output current. Test current range: 50% ~
100% rated current
Input voltage: 176Vac ~ 290Vac, rectifier max. output power: 50% rated power,
1000W
Input voltage: 90Vac ~ 176Vac, rectifier output power: linear derating power